Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T02CM05305
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/29/2003 | ELECTRIC - FINAL | Approved | ||
01/28/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245*SEE WRITE UP #170. | |
01/27/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245*/ 1) NOTE: INSTALL CLASS 'J' FUSES AT SERVICE PER PLAN | |
01/21/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245* 1.) USE PROPER SCREWS TO HOLD PANEL COVERS. 2.) PANEL SCHEDULES NOT INSTALLED. 3.) PLUG UNUSED KO'S AND INSTALL MISSING BLANK COVERS. 4.) SCREW LIGHT FIXTURES (2X4) LAYIN TO GRID. 5.) SUPPORT MC CABLE WITHIN 12" EACH TERMINATION AND AT 6' OR LESS FIXTURE WHIPS. 6.) INSTALL INSULATING BUSHINGS ON CONNECTORS WHERE USING #4 OR LARGER CONDUCTORS PER 300-4 NEC. 7.) NEED LETTER FOR USE OF MC CABLE FROM ARCH. 8.) INSTALL PROPER ADDRESS ON SERVICE FOR EACH SPACE. 9.) INSTALL FUSES SPECIFIED ON PLANS AT SERVICES. |