Permit: T02CM05305

Parcel: 11942009C

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T02CM05305

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/29/2003 ELECTRIC - FINAL Approved
01/28/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0245*SEE WRITE UP #170.
01/27/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0245*/ 1) NOTE: INSTALL CLASS 'J' FUSES AT SERVICE PER PLAN
01/21/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0245*
1.) USE PROPER SCREWS TO HOLD PANEL COVERS.
2.) PANEL SCHEDULES NOT INSTALLED.
3.) PLUG UNUSED KO'S AND INSTALL MISSING BLANK COVERS.
4.) SCREW LIGHT FIXTURES (2X4) LAYIN TO GRID.
5.) SUPPORT MC CABLE WITHIN 12" EACH TERMINATION AND AT 6' OR LESS FIXTURE WHIPS.
6.) INSTALL INSULATING BUSHINGS ON CONNECTORS WHERE USING #4 OR LARGER CONDUCTORS PER 300-4 NEC.
7.) NEED LETTER FOR USE OF MC CABLE FROM ARCH.
8.) INSTALL PROPER ADDRESS ON SERVICE FOR EACH SPACE.
9.) INSTALL FUSES SPECIFIED ON PLANS AT SERVICES.