Permit: T02CM05298

Parcel: 12710229B


Addresses:

677 N WILMOT RD


Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T02CM05298

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
04/01/2004 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection 0000*/ NEED TO SEE CONDENSATE IN BASEMENT. NEED TO SEE FN COILS AND DUCTING IN M.R.I. EQUIPMENT ROOMS 1ST FLOOR. PROVIDE SECONDARY DRAIN PANS. NEED TO SEE DUCT SMOKE DETECTORS OPERATIONAL. OK FOR CEILING TILES.
02/19/2004 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000*/ INSPECTED CONDENSATE DRAIN LINES AND REMAINING DUCT ON 2ND FLOOR. OK FOR CEILING TILES 2ND FLOOR ONLY. NEED TO SEE DUCT SMOKE DETECTORS IN RETURN AIR.
02/12/2004 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000*/ INSPECTED C-ARM ROOM. OK FOR CEILING TILES. CHECKED ANGLE IRON ON UNDERSIDE OF FIRE DAMPERS.
01/16/2004 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000*/ OK FOR CEILING TILES 2ND FLOOR NORTH OF COLUMN 'D'. OK FOR CEILING TILES 1ST FLOOR NORTH OF COLUMN 'D' AND WEST OF COLUMN 4.
09/19/2003 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000*/ INSPECTED EXHAUST AND SUPPLY IN CLOSETS AND RESTROOMS. OK TO SHEET ROCK.
07/02/2003 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000*/ 1) INSPECTION ON 1ST FLOOR MEDIUM PRESSURE 2) DUCT OK TO INSULATE
06/13/2003 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000*/PARTIAL ON SUSPENDED ROUGH DUCT. OK TO PROCEED. FIRST FLOOR.