Inspection History: ELECTRIC - TEMP POWER FOR TEST
Permit Number - T02CM05297
Inspection Description - ELECTRIC - TEMP POWER FOR TEST
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/27/2004 | ELECTRIC - TEMP POWER FOR TEST | Approved | ||
04/23/2004 | ELECTRIC - TEMP POWER FOR TEST | Partial Approval | IVRS - Inspection : See detailed listing on site.| 999*/ 1) CLOSE OFF ENTRANCE HOLES FOR W. CUMMING FEEDERS. 2) PLEASE USE LISTED CRIMPS FOR SPLICES (PANEL RHA) AND PROVIDE LETTER AUTHORIZING REDUCTION SPLICES FOR CONDUCTOR SIZES. OK TEMP POWER FOR TEST - SUBJECT TO BOND. RECEIVED LETTER FOR TORQUE. OK GROUND FAULT TEST - PROVIDE FINISHED PAPERWORK. OK PBHA, T-1, T-2, ECHA. CONTRACTOR TO MAINTAIN LOCK OUT TAG OUT AS SUBMITTED FOR SAFETY. |