Inspection Status: Approved
Inspection History: EXCAVATION/LAYOUT REBAR & ZON
| Date |
Description |
Inspector |
Results |
Comments |
| 05/02/2003 |
EXCAVATION/LAYOUT REBAR & ZON |
|
Approved |
IVRS - Inspection 0000* |
| 04/29/2003 |
EXCAVATION/LAYOUT REBAR & ZON |
|
Denied |
IVRS - Inspection 0999*/ 1) #2 90 DEGREE REBAR AT CORNER MUST OVERLAP EACH SIDE REBAR BY 20" 2) #4 VERTICAL RE-INFORCING STEEL EVERY 48" MUST BE ON CENTER 3) #5 CLEANOUT WEST END OF TRENCH |
| 04/09/2003 |
EXCAVATION/LAYOUT REBAR & ZON |
|
Denied |
IVRS - Inspection 0999*/ 1) FOOTINGS MUST BE A MINIMUM OF 24" WIDE AND AT LEAST 12" DEEP-SEEPLAN 2) REBAR OVERLAPS MUST BE A MINIMUM OF 40 ROD DIAMETERS 20" 3) REINFORCING STEEL MUST BE AT LEAST 3 INCHES FROM SOIL 4) VERTICAL REINFORCING STEEL MUST BE INSTALLED AT TIME OF INSPECTION 5) FOOTING MUST EXTEND UNDER EXISTING PORCH SLAB-24" WIDE 12" DEEP |