Permit: T02CM05251

Parcel: 110031330

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T02CM05251

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/21/2003 BUILDING - FINAL Approved IVRS - Inspection 0000*
02/20/2003 BUILDING - FINAL Denied IVRS - Inspection 0999*/ 1) NOT CORRECTED, NEXT FAILURE WILL RE-FEE
02/19/2003 BUILDING - FINAL Denied IVRS - Inspection 0999*/ 1) REMOVE TAPE FROM B-VENT ON HOT WATER HEATER 2) A/C IS OVERFUSED 3) KITCHEN GFI IS INOPERABLE AND UP BATH 4) NO FLAPPER ON DRYER VENT BOOT 5) NEED NORTH HOSE BIB 6) MAIN CONDENSATE LINE NOT HOOKED UP 7) NEED SPARK SHIELD 8) CLEANOUT SECONDARY CONDENSATE PAN