Permit: T02CM05229

Parcel: 125071900


Addresses:

2401 E 6TH ST #02

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
01/21/2004 PLUMBING - FINAL Approved IVRS - Inspection 0000*
01/20/2004 PLUMBING - FINAL Denied IVRS - Inspection 0999*
01/14/2004 PLUMBING - FINAL Denied IVRS - Inspection 0999*
12/08/2003 PLUMBING - FINAL Denied IVRS - Inspection 0999*/ 1) NO GAS PRESSURE TEST 2) CORRIGATED COPPER NOT ALLOWED ON WATER HEATER T & P LINE 3) 1" CLEARANCE REQUIRED ON WATER HEATER "B" VENT TO COMBUSTIBLES 4) PROVIDE WATER HEATER WITH COMBUSTION AIR 5) GAS LINE MUST BE ELECTRICALLY BONDED 6) WATER HEATER "B" VENT MUST EXHAUST 12" HIGHER THAN ANY VERTICAL WALL WITHIN 4' 7) SEAL AROUND OUTSIDE OUTLETS 8) LABEL ALL ELECTRICAL CIRCUITS 9) BOND WATER OR LABEL PANEL PLUMBED IN PLASTIC 10) ELECTRIC OUTLET NOT ALLOWED UNDER COUNTER TOP WITH OVERHANG GREATER THAN 6" 11) TRIM CLEANOUT TO GRADE 12) NO PLAN ON SITE 13) YOU MUST OBTAIN A GAS PERMIT FOR ADDED GAS LINE