Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/28/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
| 02/25/2003 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* #2 FINAL APPROVED PLEASE CALL FOR FINAL ONCE UNIT #1 ENERGIZED TO GIVE FINAL. |
|
| 02/24/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* 1.) FRONT RECEPTACLES ON PLAN TO BE GFI PROTECTED ? SUPPORT RIGID BY 2.) ROMEX IN STORAGE RMS TO BE PHYSICALLY PROTECTED UP TO 8' 3.) TIGHTEN OUTSIDE RECEPTACLE COVERS AND BOXES 4.) AC UNIT DISCONNECT PLUG HOLE TIGHTEN MAINTENANCE RECEPT CANNOT PUT OUTSIDE RECEPTACLES ON BATH CIR PER 99NEC 210-8. OK TO CLEAR TEC UNIT #1. |