Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: ELECTRIC - UFER
| Date |
Description |
Inspector |
Results |
Comments |
| 06/27/2003 |
ELECTRIC - UFER |
|
Approved |
IVRS - Inspection 0000* |
| 02/05/2003 |
ELECTRIC - UFER |
|
Not ready for Inspection |
IVRS - Inspection 0000*NOTE A GROUNDING ELECTRODE SYSTEM IS NEEDED FOR SECOND STRUCTURE SERVED FROM COMMON SERVICE 250-32. |