Permit: T02CM05212

Parcel: 137070500

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
11/19/2002 ELECTRIC - RECONNECT Approved IVRS - Inspection 0000*
11/12/2002 ELECTRIC - RECONNECT Denied 1.) ALL SERVICES HAVE TO BE UNLOCKED FOR INSPECTION.
2.) ALL SERVICES HAVE TO BE PERMANENTLY LABELED WITH SPACE DESIGNATION.
3.) 2ND SERVICE MISSSING A WEATHER HEAD AT SERVICE MUST.
4.) OUTSIDE RECEPTACLE NW CORNER DAMAGED. KNOCKED OVER.
5.) UNIT A NEED TO PHYSICALLY PROTECT WIRING BEHIND WATER HEATER AND CABINET AREA, BEDROOMS REQUIRE SMOKE DETECTORS. CIRCUITS IN PANEL OVER FUSED, USE 20 AMP ON #12 WIRES, 15AMP ON #14 REPLACE BROKE DEVICE PLATES.
6.) UNIT C SMOKE DETECTORS. IN BED ROOMS PROTECT WIRING BEHIND WATER HEATER AN DCABINET AREA, REPLACE DEVICE COVERS, BROKEN RECEPTACLE IN BED RM, INSTALL FUSING IN PANEL.
7.) UNIT E SMOKE DETECTORS IN BEDROOMS, DEVICE COVERS ROMEX BEHIND WATER HEATER & CABINET TO BE PROTECTED.
8.) UNIT F SMOKE DETECTOR IN BEDROOMS, PROTECT WIRING BEHIND WATER HEATER AND CABINET. CHECK CIRCUIT BREAKER FOR SIZING INSTALL ALL DEVICE COVERS.
ALL PANELS GROUNDS AND NEUTRALS TO BE SEPERATED.