Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
Permit Number - T02CM05212
Inspection Description - ELECTRIC - RECONNECT
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/19/2002 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection 0000* | |
11/12/2002 | ELECTRIC - RECONNECT | Denied | 1.) ALL SERVICES HAVE TO BE UNLOCKED FOR INSPECTION. 2.) ALL SERVICES HAVE TO BE PERMANENTLY LABELED WITH SPACE DESIGNATION. 3.) 2ND SERVICE MISSSING A WEATHER HEAD AT SERVICE MUST. 4.) OUTSIDE RECEPTACLE NW CORNER DAMAGED. KNOCKED OVER. 5.) UNIT A NEED TO PHYSICALLY PROTECT WIRING BEHIND WATER HEATER AND CABINET AREA, BEDROOMS REQUIRE SMOKE DETECTORS. CIRCUITS IN PANEL OVER FUSED, USE 20 AMP ON #12 WIRES, 15AMP ON #14 REPLACE BROKE DEVICE PLATES. 6.) UNIT C SMOKE DETECTORS. IN BED ROOMS PROTECT WIRING BEHIND WATER HEATER AN DCABINET AREA, REPLACE DEVICE COVERS, BROKEN RECEPTACLE IN BED RM, INSTALL FUSING IN PANEL. 7.) UNIT E SMOKE DETECTORS IN BEDROOMS, DEVICE COVERS ROMEX BEHIND WATER HEATER & CABINET TO BE PROTECTED. 8.) UNIT F SMOKE DETECTOR IN BEDROOMS, PROTECT WIRING BEHIND WATER HEATER AND CABINET. CHECK CIRCUIT BREAKER FOR SIZING INSTALL ALL DEVICE COVERS. ALL PANELS GROUNDS AND NEUTRALS TO BE SEPERATED. |