Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T02CM05203
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/03/2003 | ELECTRIC - INTERMEDIATE | Approved | ||
02/05/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* | |
02/03/2003 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000* 1.) RECEPTACLE INSIDE WOMENS BATHROOM BELOW NEW SWITCH THE MC CABLE HAS TO HAVE A CONNECTOR GOING INTO BOX ALSO REMOVE THE LB CONDULET CANNOT BE IN WALL. 2.) RESUPPORT J-BOX IN WOMENS BATHROOM AND RESECURE CABLE, ALSO RESUPPORT CABLE TO SWITCH. 3.) SUPPORT CABLE GOING TO SWITCH IN MENS BATHROOM. 4.) INSTALL GROUND SCREWS IN ALL METAL BOXES AND SCREW DOWN GROUND WIRE. 5.) PLAN SHOWS LIGHT SWITCH IN EXISTING BREAKROOM IS THE EXISTING SWITCH ON SOUTH WALL TO BE USED. |