Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date |
Description |
Inspector |
Results |
Comments |
| 02/18/2004 |
ELECTRIC - CABLE DROP |
|
Approved |
IVRS - Inspection 0000*SENT TO TEP ON 02/19/04AM |
| 11/13/2003 |
ELECTRIC - CABLE DROP |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ SEE NOTE INSP. 11/06/03 - CALL FOR CABLE DROP WHEN RISER INSTALLED.- OK UNDERGROUND FEEDER CONDUIT. |
| 11/12/2003 |
ELECTRIC - CABLE DROP |
|
Denied |
IVRS - Inspection 0245* FEEDER CONDUIT TO SHALLOW, SHOULD BE 18" FROM TOP OF CONDUIT TO FINISHED GRID |
| 11/06/2003 |
ELECTRIC - CABLE DROP |
|
Denied |
IVRS - Inspection 0245*/1) INSTALL RISER CONDUIT AND SUPPORT 2) 45 DEGREE MAXIMUM ANGLE FOR GROUND RODS TO BE DRIVEN PER ART 250 NEC. 3) INSTALL ADDRESS LABELS 4) SAME RESULTS FOR 2434 |