Permit: T02CM05178

Parcel: 129122280


Addresses:

1007 E 32ND ST

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
12/12/2003 PLUMBING - ROUGH, SOIL Approved 1) SOIL WTR TEST OK. 2) OK FOR BACKFILL.
12/11/2003 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection 0999*/ 1) CANNOT USE A COMBO IN A VERTICAL POSITION FOR A TRAP ARM. THIS WILL CAUSE THE OUTLET OF TRAP TO BE LOWER THAN TRAP. USE A SAN-TEE 2) FERNCO COUPLINGS NOT ALLOWED UNDER THE STRUCTURE OR ON A NEW APPLICATION USE SPECIALTY COUPLING. 3) MUST PROVIDE WATER TEST ON WASTE AND VENT SYSTEM 4) MUST STRAP DOWN ALL HORIZONTAL VENTS ABOVE CEILING. NO P-TAPE ALLOWED. 5) FOR ADDRESS 1009 E. 32ND ST.: MUST EXPOSE COVERED PLUMBING 2) MUST STRAP DOWN HORIZONTAL VENTS