Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T02CM05177

Parcel: 129121280

Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Date Description Inspector Results Comments
05/05/2004 ELECTRIC - CABLE DROP Approved IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
05/04/2004 ELECTRIC - CABLE DROP Denied IVRS - Inspection :
The service is not per code.| 210*/ 1) SEPERATE THE GROUND AND NEUTRAL BARS AT THE SUB-PANELS. THE MAIN SERVICE PANEL IS THE ONLY LOCATION WHERE GROUND AND NEUTRAL MAY BE CONNECTED 2) REMOVE THE SCOTCH COAT FROM THE GAS PIPE WHERE GROUND CLAMP IS ATTACHED 3) REMOVE THE PANEL COVERS AT THE MAIN PANEL FOR READY INSPECTION OF ALL CONNECTIONS 4) COMPLETE UFER RUN TO 2ND GAS PIPE