Inspection History: REINFORCED MASONRY PRE-GROUT

Date Description Inspector Results Comments
07/14/2003 REINFORCED MASONRY PRE-GROUT Approved IVRS - Inspection 0000*
07/03/2003 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection 0000*FIRST LIFT OK TO GROUT. CALL FOR BOND BEAM INSPECTION.
07/01/2003 REINFORCED MASONRY PRE-GROUT Denied IVRS - Inspection 0999*1) REBAR MUST BE IN CELLS AND EXTEND A MINIMUM OF 20" ABOVE LAST LAYED BLOCK FOR OVER LAP. 2) REINFORCING STEEL MUST BE IN FIRST CELL EITHER SIDE OF WINDOWS & DOORS. 3) CLEAN ALL CELLS TO BE GROUTED.