Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/13/2003 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection 0000*THIS INSPECTION WAS DONE BY RICK MYERS ON 2/12/03 | |
| 02/11/2003 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999*SOIL PIPE MUST BE FLUSH WITH THE TOP OF THE RING SO THERE ARE NO FOULING LEDGES OR SHOULDERS. THIS IS CALL A DUTCHMAN". CUT AND INSTALL DUTCHMAN ON AFFECTED CLOSET. | |
| 01/27/2003 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*1.) A KITCHEN SINK, OR BREAKROOM SINK IS NOT AN APPROVED LOCATION TO TERMINATE CONDENSATE WASTE. 2.) PLAN ON SITE SHOWS CONDENSATE TERMINATING AT A LAVATORY TAILPIECE NOT A SINK TAILPIECE. 3.) NO CITY APPROVED PLAN ON SITE. 4.) LOCATED APPROVED PLAN IN JOB TRAILER. |
|
| 01/26/2003 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999*NO APPROVED PLANS ON SITE. | |
| 01/08/2003 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* |