Permit: T02CM05147

Parcel: 136153900


Addresses:

7835 E ROGET DR

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
05/05/2003 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection 0000*
04/28/2003 EXT METAL CLIPS/EXT SHEATHING Not ready for Inspection IVRS - Inspection 0000*PROVIDE CITY APPROVED REVISIONS.
04/25/2003 EXT METAL CLIPS/EXT SHEATHING Not ready for Inspection IVRS - Inspection 0000*
04/09/2003 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection 0999*
1.) SHEAR WALL SCHEDULE NOT FOLLOWED B/1 CALLS FOR 2' SHEAR WALL AT LOCATIONS WHERE IT IS IMPOSSIBLE TO PUT IN A 2' SHEET OF OSB.
2.) NAILING SCHEDULE NOT FOLLOWED.
3.) CLARIFY WHERE HOLD DOWNS BELONG AND HOW MANY @ EACH LOCATION IS IT 8 OR 16?
04/03/2003 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection 0999*
1.) HD'S MISSING @ FRONT OF GARAGE.
2.) PLANS ARE UNCLEAR. I NEED TO KNOW WHICH PAGE OF HD REFERENCES TO USE. I NEED TO KNOW WHAT HEX NOTES 1-4 ON PAGE 2 MEAN.