Permit: T02CM05143

Parcel: 140420740


Addresses:

7250 S TUCSON BL

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
01/13/2003 ELECTRIC - INTERMEDIATE Approved
12/31/2002 ELECTRIC - INTERMEDIATE Partial Approval 1.) ID PANELS & CIRCUITS EDS UNITS LISTED #7 #6
2.) ZONE #4 ID PNL AND CIR'S EDS #5 SEAL 2" HOLE BOTTOM.
3.) ZONE #3 ID PNL AND CIR'S
4.) ZONE 2 ID PNL AND CIRS.
5.) WLEDGA COVER GUTTER LABEL PNL AND CIR'S
6.) EDEDS LABEL PNL & CIR'S
7.) WDEDS LABEL PNL & CIR'S OK FOR TEMP C OF O FOR USE OF EDS SYSTEMS, OK ON LETTER OF USE W/O UPS.
CALL FOR FINAL PRIOR TOUSE OF ANY OTHER EQUIPMENT HAVE CORRECT PLANS ON SITE FOR FINAL.
12/23/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*1.) ZOWES 3 & 5 ROUGH IN OK.
12/20/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*
12/10/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*1.) UNITED AL. DELTA AND FRONTIER AL. X-RAY TEST AREAS. OK TO POUR.
12/09/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*1.) UNDERSLAB PVC & BOXES AT WEST BAG ROOM, EAST BAG ROOM DELTA AL, NO WEST A. S WEST AL.