Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T02CM05108
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/16/2003 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000* | |
| 06/20/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) OK ROUGH ELECTRIC 2) PLEASE FINISH # 1 AND 2 OF PREVIOUS INSPECTIONS | |
| 06/18/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) FINISH ITEMS #1, 2, 4 AND 5 OF PREVIOUS INSPECTION 2) OK TO 1 SIDE ONLY | |
| 06/17/2003 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000*/ 1) PLEASE FINISH PREVIOUS INSPECTION ITEM BEFORE CALLING FOR INSPECTION OR A REFEE MAY BE APPLIED | |
| 06/16/2003 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0999*/ 1) PLEASE COMPLETE ITEM # DATED 4-10 AND 4-14 OF PREVIOUS INSPECTIONS 2) WHERE IS GROUNDING SUPPORT FOR 3/0 BOXES 3) SUPPORT UM CABLE WITHIN 12" OF BOXES 4) SUPPORT PANEL ON OTHER SIDE AND SUPPORT CABLES ABOVE PANEL 5) CLAMPING DEVICES FOR 2 GANG BOXES 370.17 6) FINISH VDV RUNS AND SUPPORT AT SERVICE 7) GROUND METAL BOXES AND 3/0 WITH GROUNDING SUPPORT 8) CONDUCTORS/CABLES TO BE 1/4" MINIMUM INTO BOXES 9) MAINTAIN FIRE THROUGH PENETRATIONS |