Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T02CM05107
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/16/2003 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000* | |
| 06/20/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) OK ROUGH ELECTRIC 2) PLEASE FINISH #1 AND 2 OF PREVIOUS INSPECTIONS | |
| 06/18/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) FINISH ITEMS #1, 2, 4 AND 5 OF PREVIOUS INSPECTION 2) OK TO 1 SIDE ONLY | |
| 06/17/2003 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000*/ 1) SEE WRITE UP #11, 12 AND 13 | |
| 06/16/2003 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0999*/ 1) PLEASE COMPLET ITEM DATED 4//03 AND 4/14/03 OF PREVIOUS INSPECTIONS 2) WHERE IS GROUNDING SUPPORT FO 3/0 BOXES ? 3) SUPPORT NM CABLE WITHIN 12" OF BOXES 4) SUPPORT PANELS ON OTHER SIDE AND SUPPORT CABLE ABOVE PANEL-DO NOT BUNDLE 5) CLAMPING DEVICES FOR 2 GANG BOXES 370.17 6) FINISH VDV RUNS AND SUPPORT AT SERVICE 7) GROUND METAL BXOES AND 3/0 WITH GROUNDING SUPPORT 8) CONDUCTORS/CABLES TO BE 1/4" MINIMIMUM INTO BOX 9) MAINTAIN FIRE PENETRATION AT THROUGH WALLS | |
| 06/13/2003 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0999*/ 1) #8 PANEL TO BE SUPPORTED BOTH SIDES #9 PANEL TO BE SUPPORTED BOTH SIDES #10 PANEL TO BE SUPPORTED BOTH SIDES |