Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 12/19/2003 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 12/18/2003 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) TIGHTEN LOOSE FITTINGS 2) INSTALL MISSING JUNCTION BOX COVER 3) FINISH SUPPORTING M/C CABLE 4) CALL ALL INSPECTIONS ( BUILDINGS) IN |
| 12/15/2003 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) FINISH CARPORT LIGHTING 2) RECEIVED LETTER FOR FEEDERS 3) IF CARPORTS ARE NOT FINISHED NEXT INSPECTION A REFEE MAY BE ISSUED |
| 12/08/2003 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) PLEASE PROVIDE A LETTER AUTHORIZING USE OF ALUMINUM FEEDER AND FINISH CARPORT LIGHTING |
| 12/03/2003 |
ELECTRIC - FINAL |
|
Partial Approval |
1) OK UF CABLE IN TRENCHES-OK TO CEMENT COVER AND BACKFILL 2) PLEASE PROVIDE LETTER FOR ALUMINIUM FEEDERS #3 OLD 3) FINISH CARPORT LIGHTING |
| 11/28/2003 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) AN APPROVED EXTENDER RING IS NEEDED FOR BOXES NOT FLUSH IN COMBUSTIBLES-AT CABINETS 370.20 2) PLEASE UNLOCK WATER HEATERS FOR INSPECTION 3) PLEASE PROVIDE A LETTER AUTHORIZING USE OF ALUMINUM FEEDER CONDUCTORS 4) NO CABLE IN TRENCH 5) TIGHTEN LOOSE FITTINGS AND SUPPORT A/C DISCONNECT BOXES |