Permit: T02CM05106

Parcel: 122181810

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T02CM05106

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/19/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
12/18/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*/ 1) TIGHTEN LOOSE FITTINGS 2) INSTALL MISSING JUNCTION BOX COVER 3) FINISH SUPPORTING M/C CABLE 4) CALL ALL INSPECTIONS ( BUILDINGS) IN
12/15/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*/ 1) FINISH CARPORT LIGHTING 2) RECEIVED LETTER FOR FEEDERS 3) IF CARPORTS ARE NOT FINISHED NEXT INSPECTION A REFEE MAY BE ISSUED
12/08/2003 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*/ 1) PLEASE PROVIDE A LETTER AUTHORIZING USE OF ALUMINUM FEEDER AND FINISH CARPORT LIGHTING
12/03/2003 ELECTRIC - FINAL Partial Approval 1) OK UF CABLE IN TRENCHES-OK TO CEMENT COVER AND BACKFILL 2) PLEASE PROVIDE LETTER FOR ALUMINIUM FEEDERS #3 OLD 3) FINISH CARPORT LIGHTING
11/28/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*/ 1) AN APPROVED EXTENDER RING IS NEEDED FOR BOXES NOT FLUSH IN COMBUSTIBLES-AT CABINETS 370.20 2) PLEASE UNLOCK WATER HEATERS FOR INSPECTION 3) PLEASE PROVIDE A LETTER AUTHORIZING USE OF ALUMINUM FEEDER CONDUCTORS 4) NO CABLE IN TRENCH 5) TIGHTEN LOOSE FITTINGS AND SUPPORT A/C DISCONNECT BOXES