Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T02CM05098

Parcel: 141301260


Addresses:

6183 S KAUFMAN DR


Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Permit Number - T02CM05098

Inspection Description - EXT METAL CLIPS/EXT SHEATHING

Inspection Status - Approved

Date Description Inspector Results Comments
12/09/2002 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection 0000*
12/05/2002 EXT METAL CLIPS/EXT SHEATHING Not ready for Inspection IVRS - Inspection 0000*/ 1) LOOSE PLYWOOD, WALK ROOF AND NAIL 2) MISSING WIND BRACING REAR WALL 3) ROOF SHEATHING PER THIS PLAN IS TO BE SPOT NAILED DO YOU HAVE A PLAN CHANGE SEE SD3 GENERAL NOTES 4) (GABLE END) BRACING TO BE DONE PER DETAIL 7/SD3 HOUSE IS 35'-00" WIDE ONE AT RIDGE, 1-6' FROM EACH SIDE OF RIDGE 3-TOTAL, 3 X BRACE AT MIDSPAN 5) 2-STORY PLAN LEFT ON JOB-BUT ALL DETAILS ARE THE SAME, CHECK YOUR ONE STORY PLAN