Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
Permit Number - T02CM05098
Inspection Description - EXT METAL CLIPS/EXT SHEATHING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/09/2002 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection 0000* | |
12/05/2002 | EXT METAL CLIPS/EXT SHEATHING | Not ready for Inspection | IVRS - Inspection 0000*/ 1) LOOSE PLYWOOD, WALK ROOF AND NAIL 2) MISSING WIND BRACING REAR WALL 3) ROOF SHEATHING PER THIS PLAN IS TO BE SPOT NAILED DO YOU HAVE A PLAN CHANGE SEE SD3 GENERAL NOTES 4) (GABLE END) BRACING TO BE DONE PER DETAIL 7/SD3 HOUSE IS 35'-00" WIDE ONE AT RIDGE, 1-6' FROM EACH SIDE OF RIDGE 3-TOTAL, 3 X BRACE AT MIDSPAN 5) 2-STORY PLAN LEFT ON JOB-BUT ALL DETAILS ARE THE SAME, CHECK YOUR ONE STORY PLAN |