Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/23/2003 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000*SENT TO TEP ON 4/30/03 AT 9:15AM OK TO CLEAR. OK TO CLEAR TEMP SERVICE OK CABLE DROP. UNITS #1 & 2. |
|
| 01/22/2003 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0245*COULD NOT LOCATE APPROVED PLANS. | |
| 01/17/2003 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0245*1.) COULD NOT LOCATE PLANS. 2.) CONDUIT USED FOR SLEEVES MUST HAVE BUSHED CONNECTORS AT POINT OF ENTRY OF ROMEX TO PROTECT CABLE FROM ABRASION. SEE ART 300-15-C AND 300-16 NEC. 3.) REPLACE BOXES WITH BROKEN NAIL SUPPORT TABS. 4.) DRYWALL SCREWS NOT ALLOWED THRU PLASTIC BOXES AS SUPPORT. 110-3NEC. |