Permit: T02CM05079

Parcel: 124080360


Addresses:

1517 E 8TH ST #01

Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Date Description Inspector Results Comments
02/10/2003 ELECTRIC - CABLE DROP Approved IVRS - Inspection 0000*SENT TO TEP ON 2/10/03 AT 9:15AM OK TO CLEAR CABLE DROP ONLY.
1.) REPLACE SHEET ROCK SCREWS W/1/4" MIN LAG BOLTS.
2.) GROUND THE CHASE NIPPLES IN GUTTER.
02/07/2003 ELECTRIC - CABLE DROP Partial Approval IVRS - Inspection 0000*
02/06/2003 ELECTRIC - CABLE DROP Denied IVRS - Inspection 0215*/ NOTICE: 1) CALL FOR TEMPORARY SERVICE INSPECTION. LEAVE COVERS OFF GUTTER AND PANELS FOR INSPECTION. 2) THE PLAN CALLS FOR A ON PIECE (SES) SERVICE ENTRANCE PANEL. THE EQUIPMENT INSTALLED MEETS CODE-BUT DOES NOT MEET. THE ENGINEERS REQUIREMENTS. PLEASE INFORM THE ENGINEER OF RECORD AND HAVE HIM ISSUE A LETTER ON HIS STATIONARY LETTER HEAD APPROVING THE SUBSTITUDED PANELS 3) LEAVE A SHORT SAMPLE OF THE RISER WIRE WITH ALL MARKING CLEARLY VISIBLE