Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/10/2003 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection 0000*SENT TO TEP ON 2/10/03 AT 9:15AM OK TO CLEAR CABLE DROP ONLY. 1.) REPLACE SHEET ROCK SCREWS W/1/4" MIN LAG BOLTS. 2.) GROUND THE CHASE NIPPLES IN GUTTER. |
|
| 02/07/2003 | ELECTRIC - CABLE DROP | Partial Approval | IVRS - Inspection 0000* | |
| 02/06/2003 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection 0215*/ NOTICE: 1) CALL FOR TEMPORARY SERVICE INSPECTION. LEAVE COVERS OFF GUTTER AND PANELS FOR INSPECTION. 2) THE PLAN CALLS FOR A ON PIECE (SES) SERVICE ENTRANCE PANEL. THE EQUIPMENT INSTALLED MEETS CODE-BUT DOES NOT MEET. THE ENGINEERS REQUIREMENTS. PLEASE INFORM THE ENGINEER OF RECORD AND HAVE HIM ISSUE A LETTER ON HIS STATIONARY LETTER HEAD APPROVING THE SUBSTITUDED PANELS 3) LEAVE A SHORT SAMPLE OF THE RISER WIRE WITH ALL MARKING CLEARLY VISIBLE |