Permit: T02CM05078

Parcel: 133243830

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T02CM05078

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
04/15/2003 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*STRAP EMT CONDUIT BELOW SERVICE PANEL
MUST BE DONE WITHIN 3' OF ENCLOSURE
2.) CORRECTLY MARK PANEL SCHEDULE "SHED" NOT GENERAL POWER OR SMOKE DETECTORS POWER OR SMOKE DETECTORS.
3.) SINCE THE SHED IS INDEPENDENT OF HOUSE IT NEEDS ITS OWN GROUND SYSTEM.
4.) FINISH LIGHTS AND RECEPTACLES AND CALL FOF FINALS.
02/20/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*