Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 03/23/2004 |
MECHANICAL - ABOVE CEILING |
|
Approved |
IVRS - Inspection 0000* |
| 03/12/2004 |
MECHANICAL - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*/ NORTH FIRE DAMPER ROOM 105 SLEEVE IS TOO SHORT. RET. ANGLES ARE COVERING BREAKAWAY JOINT. |
| 03/09/2004 |
MECHANICAL - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) LEAVE ANGLES ONE SIDE. WANT TO SEE HOLE IN WALL, STUBS AS FRAMED, ETC. 2) REMOVE SCREWS FROM BREAK AWAY JOINTS. |
| 03/05/2004 |
MECHANICAL - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) REMOVE RETAINING ANGLES FROM FIRE DAMPER INST. PULL BACK EXTERNAL DUCT WRAP. RETAINING ANGLES LOCATE UP AGAINST FIRE DAMPERS SLEEVE. 2) WANT TO SEE BREAK AWAY JOINTS, HARD DUCT IN AND OUT OF SLEEVE, PENETRATION IN WALL. CANNOT DO A FIRE DAMPER INSP. ON ONE VISIT. LEAVE ANGLES OFF OF ONE SIDE. |