Permit: T02CM05076

Parcel: 116122030


Addresses:

855 N MELROSE AV 02

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
03/23/2004 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection 0000*
03/12/2004 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000*/ NORTH FIRE DAMPER ROOM 105 SLEEVE IS TOO SHORT. RET. ANGLES ARE COVERING BREAKAWAY JOINT.
03/09/2004 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000*/ 1) LEAVE ANGLES ONE SIDE. WANT TO SEE HOLE IN WALL, STUBS AS FRAMED, ETC. 2) REMOVE SCREWS FROM BREAK AWAY JOINTS.
03/05/2004 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000*/ 1) REMOVE RETAINING ANGLES FROM FIRE DAMPER INST. PULL BACK EXTERNAL DUCT WRAP. RETAINING ANGLES LOCATE UP AGAINST FIRE DAMPERS SLEEVE. 2) WANT TO SEE BREAK AWAY JOINTS, HARD DUCT IN AND OUT OF SLEEVE, PENETRATION IN WALL. CANNOT DO A FIRE DAMPER INSP. ON ONE VISIT. LEAVE ANGLES OFF OF ONE SIDE.