Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 01/08/2003 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 01/07/2003 |
FRAMING |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) SAME AS LAST INSPECTION |
| 01/06/2003 |
FRAMING |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) PUT GAS STUB IN A BOX 2) CHANGE HANGER FROM THA 418 TO 1465 POUNDS HGUS 26-2 3585 POUNDS USE ALL 16D COMMONS AT GARAGE FLOOR TRUSS TO GIRDER |
| 01/03/2003 |
FRAMING |
|
Partial Approval |