Permit: T02CM05054

Parcel: 138170720

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
01/08/2003 FRAMING Approved
12/05/2002 FRAMING Partial Approval IVRS - Inspection 0000*/ 1) FRAMING OK WHEN ELECTRIC CALC'S ARE APPROVED FOR ELECTRIC FURNACE AND WATER HEATER 2) NEED ELECTRIC CALC'S TO OK CHANGING TO ELECTRIC FURNACE AND WATER HEATER OK TO INSULATE AND INSTALL DRYWALL
12/04/2002 FRAMING Not ready for Inspection IVRS - Inspection 0000*/ 1) REPLACE MISSING FIREBLOCKS 2) INSTALL MISSING ELECTRIC BOX 3) INSTALL BANG PLATES ELECTRIC 4) HAVE COPY OF GAS/ELECTRIC OPTIONS FOR VERIFICATION 6) STOPPED INSPECTION