Permit: T02CM05052

Parcel: 127035510

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T02CM05052

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/16/2003 MECHANICAL - FINAL Approved IVRS - Inspection 0000*ALL CORRECTIONS HAVE BEEN MADE OK FOR C OF O
01/15/2003 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*
STILL MISSING SCREEN ON INTAKE lOUVER UNIT #1 SEAL AROUND REFER LINE PENETRATIONS & REPAIR TORN INSULATION.
HOOK UP OVERFLOW SENSOR UNIT #3.
HOOK UP ELECTRICAL TO FAN COIL #1
PROVIDE SCREWS WHERE SINGLE WALL VENT PIPE CONNECTS TO DOUBLE WALL UNIT #3 & REPAIR DAMAGED VENT CAP ALSO PROVIDE MIN. 1" CLEARANCE AROUND BATH FLUE VENTS THRU ROOF.
01/08/2003 MECHANICAL - FINAL Denied IVRS - Inspection 0999*
1.) COMBUSTION AIR LOWERS UPSIDE DOWN. PROVIDE SCREEN ON LOUVERS.
2.) HOOK UP OVERFLOW SENSORS ON CONDENSATE PUMPS.
3.) PROVIDE SCREWS IN FURNACE VENTS.
4.) REPAIR OR REPLACE GAS SHUT OFF VALVE UNIT #3.
5.) USE A BUSHING OR CHASE NIPPLE ON POWER CHASE NIPPLE ON POWER CORD FOR FURNACE #2 & 3.
6.) GAS FLEX CANNOT PENETRATE THE CABINET OF FURNACE.