Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T02CM05052
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/16/2003 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000*ALL CORRECTIONS HAVE BEEN MADE OK FOR C OF O | |
| 01/15/2003 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000* STILL MISSING SCREEN ON INTAKE lOUVER UNIT #1 SEAL AROUND REFER LINE PENETRATIONS & REPAIR TORN INSULATION. HOOK UP OVERFLOW SENSOR UNIT #3. HOOK UP ELECTRICAL TO FAN COIL #1 PROVIDE SCREWS WHERE SINGLE WALL VENT PIPE CONNECTS TO DOUBLE WALL UNIT #3 & REPAIR DAMAGED VENT CAP ALSO PROVIDE MIN. 1" CLEARANCE AROUND BATH FLUE VENTS THRU ROOF. |
|
| 01/08/2003 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999* 1.) COMBUSTION AIR LOWERS UPSIDE DOWN. PROVIDE SCREEN ON LOUVERS. 2.) HOOK UP OVERFLOW SENSORS ON CONDENSATE PUMPS. 3.) PROVIDE SCREWS IN FURNACE VENTS. 4.) REPAIR OR REPLACE GAS SHUT OFF VALVE UNIT #3. 5.) USE A BUSHING OR CHASE NIPPLE ON POWER CHASE NIPPLE ON POWER CORD FOR FURNACE #2 & 3. 6.) GAS FLEX CANNOT PENETRATE THE CABINET OF FURNACE. |