Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/16/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*ENGINEER PROVIDED LETTER FOR FUSEING NLN 200 ARE OK PER LETTER OK FINAL. | |
| 01/15/2003 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000* | |
| 01/14/2003 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*PLEASE FINISH ITEMS #3,4,5 OF PREVIOUS INSPECTION. | |
| 01/08/2003 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*1.) AN APPROVED EXTENDER RING IS NEEDED WHERE MORE THAN 1/4" FROM BOX TO DEVICE. 2.) A DISCONNECTING MEANS IS NEEDE FOR INSTA HOT WATER HEATER. 3.) PROTECT SEALTITE FROM SHARP EDGES WHERE PASSING THROUGH METAL. 4.) AN APPROVED CONNECTING TAPS IN GUTTER. SPLIT BOLT ONLY LISTED FOR 2 CONDUCTORS. ALSO REMOVE OLD WIRES BACK TO TAP CONNECTION. 5.) PLEASE VERIFY TYPE FUSES FOR MAIN DISCONNECT. 6.) PLEASE VERIFY FUSING AND CONDUCTOR SIZE TO A/C UNIT.S |
|
| 01/03/2003 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000* |