Permit: T02CM05052

Parcel: 127035510

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T02CM05052

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/16/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*ENGINEER PROVIDED LETTER FOR FUSEING NLN 200 ARE OK PER LETTER OK FINAL.
01/15/2003 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*
01/14/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*PLEASE FINISH ITEMS #3,4,5 OF PREVIOUS INSPECTION.
01/08/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1.) AN APPROVED EXTENDER RING IS NEEDED WHERE MORE THAN 1/4" FROM BOX TO DEVICE.
2.) A DISCONNECTING MEANS IS NEEDE FOR INSTA HOT WATER HEATER.
3.) PROTECT SEALTITE FROM SHARP EDGES WHERE PASSING THROUGH METAL.
4.) AN APPROVED CONNECTING TAPS IN GUTTER. SPLIT BOLT ONLY LISTED FOR 2 CONDUCTORS. ALSO REMOVE OLD WIRES BACK TO TAP CONNECTION.
5.) PLEASE VERIFY TYPE FUSES FOR MAIN DISCONNECT.
6.) PLEASE VERIFY FUSING AND CONDUCTOR SIZE TO A/C UNIT.S
01/03/2003 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*