Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T02CM05048
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/05/2003 | PLUMBING - FINAL | Approved | IVRS - Inspection 0000*/ OK FOR C OF O. | |
08/04/2003 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999*/1) TRAP ARM CAN ONLY HAVE 1 - 90 DEGREE. IF YOU EXCEED 1 - 90 DEGREE, THEN A C.O. IS REQUIRED ON TRAP ARM. 1 - 90 DEGREE & 1 - 45 DEGREE = 135 DEGREE. | |
08/01/2003 | PLUMBING - FINAL | Denied | 1) MUST USE A SAN-TEE FOR P.O.C. OF 2" TRAP ARM 2) CAN NOT CONNECT CONDENSATE DRAIN TO HAND SINK. TAKE THIS DRAIN AND INDIRECT IT TO MOP SINK |