Permit: T02CM05048

Parcel: 13015001A


Addresses:

4690 E 22ND ST


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T02CM05048

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/05/2003 PLUMBING - FINAL Approved IVRS - Inspection 0000*/ OK FOR C OF O.
08/04/2003 PLUMBING - FINAL Denied IVRS - Inspection 0999*/1) TRAP ARM CAN ONLY HAVE 1 - 90 DEGREE. IF YOU EXCEED 1 - 90 DEGREE, THEN A C.O. IS REQUIRED ON TRAP ARM. 1 - 90 DEGREE & 1 - 45 DEGREE = 135 DEGREE.