Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T02CM05044
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/16/2002 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*Sent to tep on 12/17/02 at 9:15am ok to clear power connections. | |
12/12/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*TRACK LIGHTING CANNOT BE SUPPORTED ON CEILING TILE. 2.) IMPROPER WIRING FROM TRACK LIGHTING TO J-BOXES OMIT OPEN J-BOXES BO STRAIGHT TO FIXTURES. 3.) SEIMIC WIRE SUPPORTS REQUIRED FOR TRACK LIGHTING. 4.) MISSING POWER POLES AT FRONT COUNTER. 5.) NEED TO LABEL PANEL SCHEDULE. 6.) MISSING SW COVER ON NEW WALL. |