Permit: T02CM05002

Parcel: 117083360


Addresses:

860 S MEYER AV

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
10/22/2003 MECHANICAL - FINAL Approved IVRS - Inspection 0000*
10/20/2003 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*/ SAM SUNG ROOF TOP COND. 1) INSULATE SUCTION LINE, ESPECIALLY DOWN THRU ROOF 2) NO EXPOSED CONTROL WIRING 3) LEAVE UNIT PROPERLY FUSED. 4) PAINT PVC 5) TRAP CONDENSATE LINE-BLOCK AND CLAMP AS NECESSARY 6) IMPROPER SIZE GAS FLEX LINE AT UNIT. SEE TABLE 3D-2 FOR SIZING