Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
11/29/2002 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection 0000*
11/25/2002 EXT METAL CLIPS/EXT SHEATHING Partial Approval IVRS - Inspection 0000*
11/21/2002 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection 0999*/ 1) ITEMS FROM 11/17/02 NOT COMPLIED WITH 1, 2, AND 4 2) DRY IN AT YOUR OWN RISK
11/19/2002 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection 0999*/ 1) HOUSE IS NOT PER APPROVED SITE PLAN-ADDITIONAL PORCH ADDED TO FRONT OF HOUSE 2) HEADERS ARE NOT PERPLAN-PLAN CALLS FOR DIMENTIONAL LUMBER TIMER STRAN USED. PROVIDE ARCHITECT OF RECORD AND CITY OF TUCSON PLAN REVISION 3) INTERIOR SHEAR NOT PER 6/SD2 4) ALL ADDED ANCHOR BOLTS MUST BE EPOXY SET WITH SPECIAL INSPECTION SEE GENERAL NOTES S-1 5) FINGER JOINTED LUMBER NOT ALLOWED IN X BRACE 6) 7/SD3 KNEE BRACES REQUIRE "T" BRACE STRUNG BACK OVER 5'-9"