Permit: T02CM04981

Parcel: 123130390


Addresses:

931 E HAMPTON ST


Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T02CM04981

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
11/26/2002 FRAMING Approved IVRS - Inspection 0000*
11/21/2002 FRAMING Denied IVRS - Inspection 0999*/ 1) SILL PLATE EAST WALL REQUIRES ANCHOR BOLTS WITHIN 12" OF EACH SIDE OF SPLICE 2) ELECTRIC CONDUIT MUST BE 18" BELOW GRADE 3) SEPARATE STRUCTURE REQUIRES ELECTRIC SUB PANEL TO HAVE SEPARATE GROUNDING SYSTEM INSTALL TWO EACH 8 FOOT GROUND RODS 6 FEET APART CONNECTED TO SUB PANEL WITH AN APPROVED #4 CONDUCTOR 4) ALL METAL ELECTRIC BOXES MUST BE GROUNDED 5) CONNECT ALL GROUND WIRES IN EACH ELECTRIC BOX AND SECURE WITH AN APPROVED FASTENER 6) ALL WIRES MUST TERMINATE IN APPROVED ELECTRIC BOXES
11/20/2002 FRAMING Not ready for Inspection IVRS - Inspection 0000*/ 1) BLDG OVER HANG CAN ONLY PROJECT 1' INTO 3' SIDE YARD MINIMUM SETBACK, WHERE IS PROPERTY LINE ? 2) BOND ALL METAL ELECTRIC BOXES 3) SERVICE PANEL MAXIMUM SIX SWITCHES TO SHUT DOWN SERV. WITHOUT A MAIN DISCONNECT YOU CAN'T ADD ANY MORE BREAKERS 4) NON METALLIC CONDUIT TO BE 18" BELOW GRADE, SCHE. 80 CONDUIT REQUIRED ABOVE GRADE 5) TRUSSES TO BE X BRACED, USING NAILS IN SHEAR 6) 3/4" CONDUIT IN RENCH IS DAMAGED