Inspection History: SHEET ROCK NAILING
Permit Number - T02CM04980
Inspection Description - SHEET ROCK NAILING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/25/2003 | SHEET ROCK NAILING | Approved | IVRS - Inspection 0000* | |
| 03/10/2003 | SHEET ROCK NAILING | Partial Approval | IVRS - Inspection 0000*/ 1) WHITE WIRE RUNNING TO DOUBLE POLED BREAKER SHOULD BE COLORED TO INDICATE HOT USE 2) MARK FUNCTION OF ALL BREAKERS ON PANEL DEAD FRONT 3) STUD BAY CONTAINING SWITCHES, SOUTH OF GARAGE TO HOUSE PEDESTRIAN DOOR, MUST BE SHEET ROCKED 4) ALL OUTLET AND SWITCH BOXES MUST BE COVERED AND HOT FOR ELECTRIC FINAL 5) 20 AMP WIRE HANGING FROM CEILING MUST BE PROPERLY CONNECTED TO A FIXTURE OR TERMINATED IN A CLOSED BOX 6) SHEET ROCK INSTALL NOT COMPLETE SOUTH OF AND ABOVE THE WEST PEDESTRIAN DOOR |