Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T02CM04979
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/25/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*/ 1) OK FOR PERMANENT C OF O | |
06/12/2003 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*/ 1) IDENTIFY/MARK ALL SERVICE DISCONNECTS. LABEL WITH FLOOR AND PANEL SERVED. ID A/C DISCONNECTS-BOTH ENDS 2) STRAP LIQUID TITE FLEX WITHIN 12" OF DISCONNECTS 3) STRAP FLEX CONDUIT AT WATER HEATER 4) APPROVED FOR TEMP C OF O |