Permit: T02CM04979

Parcel: 117120460


Addresses:

30 N CHURCH AV


Inspection Status: Approved

Inspection History: ELECTRIC - TEMP POWER FOR TEST

Permit Number - T02CM04979

Inspection Description - ELECTRIC - TEMP POWER FOR TEST

Inspection Status - Approved

Date Description Inspector Results Comments
05/19/2003 ELECTRIC - TEMP POWER FOR TEST Approved
05/16/2003 ELECTRIC - TEMP POWER FOR TEST Denied IVRS - Inspection 0215* 1) BOND TRANSFORMERS TO COLD WATER PIPE AND SPRINKLER PIPE 2) GROUND RODS S/B 3/4'. RE RUN THE " AFTER'' GROUND UNSPLICED 3) USE REJETION CHIPS IN DISCONNNECT SWITCHES. 4) MAKE UP J. BOXES 2ND FLOOR. 5) ADD SWITCH & LIGHT IN EQUIPMENT ROOM ABOVE BATHROOMS. 6) PANEL DIRECTORIES INDEXES.
05/13/2003 ELECTRIC - TEMP POWER FOR TEST Not ready for Inspection IVRS - Inspection 0000*RECALL HAVE PLAN E4 AND ELECTRICAL CONTRACTOR REP. ON SITE.