Inspection Status: Approved
Inspection History: ELECTRIC - TEMP POWER FOR TEST
| Date |
Description |
Inspector |
Results |
Comments |
| 05/19/2003 |
ELECTRIC - TEMP POWER FOR TEST |
|
Approved |
|
| 05/16/2003 |
ELECTRIC - TEMP POWER FOR TEST |
|
Denied |
IVRS - Inspection 0215* 1) BOND TRANSFORMERS TO COLD WATER PIPE AND SPRINKLER PIPE 2) GROUND RODS S/B 3/4'. RE RUN THE " AFTER'' GROUND UNSPLICED 3) USE REJETION CHIPS IN DISCONNNECT SWITCHES. 4) MAKE UP J. BOXES 2ND FLOOR. 5) ADD SWITCH & LIGHT IN EQUIPMENT ROOM ABOVE BATHROOMS. 6) PANEL DIRECTORIES INDEXES. |
| 05/13/2003 |
ELECTRIC - TEMP POWER FOR TEST |
|
Not ready for Inspection |
IVRS - Inspection 0000*RECALL HAVE PLAN E4 AND ELECTRICAL CONTRACTOR REP. ON SITE. |