Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/17/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
| 03/12/2003 | ELECTRIC - FINAL | Partial Approval | SERVICE APPROVED. FINAL SERVICE SUBJECT TO PROJECT. FINAL. |
|
| 03/11/2003 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000*ONLY A SERVICE INSPECTION WAS REQUESTED 1.) SERVICE NEEDS PERMANENT ADDRESS. 2.) THE 3" GRD BUSHING BETWEEN METER & GUTTER TO BE #2 COPPER NOT #6. 3.) FINISH THE GROUND ELECT CONDUCTOR TIE INTO GUTTER NEUT AND GROUND LUG ON GUTTER. 4. FINISH TRMINATION OF BLDG PANELS INTO GUTTER 5.) CONCRETE BLOCK IN FRONT OF 1ST PANEL VIOLATES CLEARANCE REQUIREMENTS 99 NEC 110-26. 6.) A BOND FOR TEMP POWER REQUIRED FOR TEMP SERVICE. |