Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date |
Description |
Inspector |
Results |
Comments |
| 12/06/2002 |
EXT METAL CLIPS/EXT SHEATHING |
|
Approved |
IVRS - Inspection 0000* |
| 12/05/2002 |
EXT METAL CLIPS/EXT SHEATHING |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) ITEMS 1, 2 AND 3 FROM PREVIOUS INSPECTION ARE COMPLETED |
| 12/04/2002 |
EXT METAL CLIPS/EXT SHEATHING |
|
Denied |
IVRS - Inspection 0950*/ 1) DOUBLE SHEARWALL 5 REQUIRES ANCHOR BOLTS AT 24" ON CENTER SEE NOTES PAGE A-5. ALSO NAIL OSB SHEATHING AT 4" ON CENTER AT WEBS 2) PROVIDE HILTI QUICK BOLT II ICBO REPORT FOR HOLDOWN ANCHORS 3) HEADERS ARE NOT PER PLAN. BUILD TO PLAN OR HAVE PLAN REVISED TO ASBUILT 4) EXTERIOR BEARING STUDS NOTCHED GREATER THAN 7/8" FOR WIND BRACES, REPLACE 5) NO LADDER ACCESS FOR ROOF 6) STOPPED INSPECTION |
| 12/03/2002 |
EXT METAL CLIPS/EXT SHEATHING |
|
Denied |
IVRS - Inspection 0925*/ 1) NO LOT # OR ADDRESS 2) NO PLANS/PERMIT OR TRUSS DRAWINGS 3) NO LADDER ACCESS TO ROOF |