Permit: T02CM04966

Parcel: 138242860

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
12/06/2002 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection 0000*
12/05/2002 EXT METAL CLIPS/EXT SHEATHING Partial Approval IVRS - Inspection 0000*/ 1) ITEMS 1, 2 AND 3 FROM PREVIOUS INSPECTION ARE COMPLETED
12/04/2002 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection 0950*/ 1) DOUBLE SHEARWALL 5 REQUIRES ANCHOR BOLTS AT 24" ON CENTER SEE NOTES PAGE A-5. ALSO NAIL OSB SHEATHING AT 4" ON CENTER AT WEBS 2) PROVIDE HILTI QUICK BOLT II ICBO REPORT FOR HOLDOWN ANCHORS 3) HEADERS ARE NOT PER PLAN. BUILD TO PLAN OR HAVE PLAN REVISED TO ASBUILT 4) EXTERIOR BEARING STUDS NOTCHED GREATER THAN 7/8" FOR WIND BRACES, REPLACE 5) NO LADDER ACCESS FOR ROOF 6) STOPPED INSPECTION
12/03/2002 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection 0925*/ 1) NO LOT # OR ADDRESS 2) NO PLANS/PERMIT OR TRUSS DRAWINGS 3) NO LADDER ACCESS TO ROOF