Permit: T02CM04944

Parcel: 121110050


Addresses:

5001 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/06/2003 ELECTRIC - FINAL Approved OK FOR TEMP C OF O
12/30/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*NOTES OK FINAL & C OF O SUJBECT TO RECEIPT OF LETTER PER ITEM #4 LAST INSPECTION.
12/11/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0245*
1.) ROMEX NOT SUPPORT PER N.E.C. OFFICE AREAS AND ABOVE PANEL "A".
2.) CAN LIGHTS NEED 1 SIEZMIC PER CAN TO STRUCTURE.
3.) REPAIR & RESUPPORT 8' STRIP FLOURSCENT FIXTURES MTD. TO GRID.
4.) NEED LETTER FROM L-11 LICENSED CONTR. TO ASSUME RESPONSIBILTY FOR THE ENTERGRITY OF THE WIRING ON THIS PROTECT FOR SAFE & WORKING SYSTEM.
11/29/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0245*NO COMPLIANCE WITH WRITE UP LAST INSP. 11-20-02.
2.) ROMEX NOT SUPPORTED PER NEC. ART 336-18.
3.) USE LISTED CONNECTORS FOR ROMEX TERMINATIONS INTO J-BOXES ETC. 110-3 NEC.
4.) NEED APPROVED REVISIONS OF PLANS TO REFLECT ACTUAL INSTALLATION OF ELECTRICAL DUE TO VALUE ENGINEERING ON JOB SITE.
5.) A RE-INSPECTION FEE WILL BE ASSESED NEXT INSPECTION IF NOT IN COMPLIANCES.