Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/06/2003 | ELECTRIC - FINAL | Approved | OK FOR TEMP C OF O | |
| 12/30/2002 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*NOTES OK FINAL & C OF O SUJBECT TO RECEIPT OF LETTER PER ITEM #4 LAST INSPECTION. | |
| 12/11/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245* 1.) ROMEX NOT SUPPORT PER N.E.C. OFFICE AREAS AND ABOVE PANEL "A". 2.) CAN LIGHTS NEED 1 SIEZMIC PER CAN TO STRUCTURE. 3.) REPAIR & RESUPPORT 8' STRIP FLOURSCENT FIXTURES MTD. TO GRID. 4.) NEED LETTER FROM L-11 LICENSED CONTR. TO ASSUME RESPONSIBILTY FOR THE ENTERGRITY OF THE WIRING ON THIS PROTECT FOR SAFE & WORKING SYSTEM. |
|
| 11/29/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245*NO COMPLIANCE WITH WRITE UP LAST INSP. 11-20-02. 2.) ROMEX NOT SUPPORTED PER NEC. ART 336-18. 3.) USE LISTED CONNECTORS FOR ROMEX TERMINATIONS INTO J-BOXES ETC. 110-3 NEC. 4.) NEED APPROVED REVISIONS OF PLANS TO REFLECT ACTUAL INSTALLATION OF ELECTRICAL DUE TO VALUE ENGINEERING ON JOB SITE. 5.) A RE-INSPECTION FEE WILL BE ASSESED NEXT INSPECTION IF NOT IN COMPLIANCES. |