Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T02CM04942
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/06/2002 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection 0000* | |
12/05/2002 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection 0245*1.) LAY IN GRID FIXTURES NEED TO BE SCREWED TO GRID (2) EACH FIXTURES. PER NEC. 2.) INSULATING BUSHINGS REQUIRED ON CONDUIT CONNECTORS IN J-BOX FOR PANEL FEEDERS ABOVE CEILING. 300-4 NEC. 3.) BOND J BOX FOR PANELJ FEEDERS PER ART 250 NEC. |