Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T02CM04942

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
12/06/2002 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection 0000*
12/05/2002 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0245*1.) LAY IN GRID FIXTURES NEED TO BE SCREWED TO GRID (2) EACH FIXTURES. PER NEC. 2.) INSULATING BUSHINGS REQUIRED ON CONDUIT CONNECTORS IN J-BOX FOR PANEL FEEDERS ABOVE CEILING. 300-4 NEC.
3.) BOND J BOX FOR PANELJ FEEDERS PER ART 250 NEC.