Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
11/14/2002 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
11/13/2002 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0245*
1. USE LISTED STRAPS FOR MC CABLE 110-3 NEC.
2.) SUPPORT MC WITHIN 12" EACH TERMINATION PER NEC.
3.) PROVIDE LETTER FROM ARCT. ALLOWING USE OF MC CABLE IN LIEU OF EMT AS SPECIFIED ON PLAN.