Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date |
Description |
Inspector |
Results |
Comments |
| 11/05/2002 |
ELECTRIC - RECONNECT |
|
Approved |
IVRS - Inspection 0000*SENT TO TEP ON 11/5/02 AT 9:15AM ALL ITEMS EXCEPT DEAD FRONT COVER FOR SERVICE PNL COMPLETE. OK TO CLEAR RECONNECT. |
| 11/04/2002 |
ELECTRIC - RECONNECT |
|
Not ready for Inspection |
IVRS - Inspection 0000*PARTIAL ALL ITEMS EXCEPT DEAD FRONT COVER FOR SERVICE PNL COMPLETE. OK TO CLEAR RECONNECT |
| 11/01/2002 |
ELECTRIC - RECONNECT |
|
Denied |
IVRS - Inspection 0999* |
| 10/28/2002 |
ELECTRIC - RECONNECT |
|
Denied |
IVRS - Inspection 0215*1.) INSTALL NEW GROUNDING SYSTEM WITH TWO GROUND RODS 5/8' X 8') #6 BARE COPPER CONDUCTOR RUN UNSPLICED (UNCUT) FROM PANEL NEUTRAL TO THE GAS PIPE TO THE GROUND RODS, AND TO COLD WATER PIPE. 2.) REPAIR EMT CONDUIT AT REAR WEST WING OF BLDG. 3.) INSTALL PANEL COVER (DEAD FRONT) OVER CIRCUIT BREAKERS. 4.) INSTALL ALL MISSING LIGHT FIXTURES. 5.) PLACE ADDRESS NUMBERS ON BUILDING. |
| 10/25/2002 |
ELECTRIC - RECONNECT |
|
Denied |
IVRS - Inspection 0920* |
| 10/22/2002 |
ELECTRIC - RECONNECT |
|
Cancelled |
IVRS - Ri canceled |