Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/24/2003 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000* | |
| 12/20/2002 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999*1.) UNIT IS STILL OVERFUSED 25 AMP IS MAX. 2.) PROVIDE A ROOF JACK WHERE CONDENSATE DRAIN PENETRATES THE ROOF. PAINT EXPOSED PVC W/LATEX PAINT STRAP PVC TO WALL. RECALL FOR INSPECTION. |
|
| 10/28/2002 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999*UNIT OVERFUSED 25 AMP IS MAX. PROVIDE CONDENSATE DRAIN LINE. PROVIDE A ROOF JACK WHERE GAS LINE PENETRATES THE ROOF. GAS FLEX TO FURNACE CANNOT EXCEED 3' IN LENGTH. |