Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 01/24/2003 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 01/23/2003 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) BLOCK GARAGE PER 31/S1-2 AND INTERIOR BEARING PER 33/S1-2 |
| 01/22/2003 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) DO NOT COVER KITCHEN GLB AND POST 2) HOUSE IS NOT BUILT PER PLAN. PLAN CALLS FOR 2 POINT BEARING TJI. 3 POINT BEARING OPEN WEB TRUSSES INSTALLED WITH AN INTERNAL BEARING WALL AND A GLU LAM BEAM IN KITCHEN AREA PROVIDE A CITY APPROVED REVISED COMPLETE FRAME PLAN SHOWING ALL STRUCTURE, BEAMS AND POSTS. PROVIDE CITY OF TUCSON APPROVED TRUSS DRAWINGS FOR FLOOR TRUSSES. PROVIDE FOUNDATION PLAN REVISION OR CERTIFICATION FROM ENGINEER OF RECORD THAT EXISTING FOUNDATION WILL BEAR INTERNAL BEARING WALLS |
| 01/21/2003 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) HIP HANGERS MISSING AT 4 TRUSSES IN GARAGE 2) FIRE BLOCK BROKEN AT DROP CEILING LAUNDRY 3) 2ND FLOOR FRAME NOT PER PLAN, POST AND BEAM NOT ON PLAN AND FOUNDATION NOT REINFORCED FOR INTERIOR BEARING WALL 4) PLUMBING OUTSIDE OF WALL CAVITY AT KITCHEN 5) NORTH WEST HIP HANGER 2ND FLOOR NOT NAILED |
| 01/17/2003 |
FRAMING |
|
Denied |
IVRS - Inspection 0925*/ 1) HOLDOWN BOLTS LOOSE AT GARAGE 2) NO PLANS/PERMIT 3) STOPPED INSPECTION |
| 01/10/2003 |
FRAMING |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) WE DO NOT DO INTERMEDIATE TRADE INSPECTION PRIOR TO INSTALLATION OF STUCCO LATH |