Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/06/2003 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000* | |
| 12/19/2002 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999* 1.) PAINT EXPOSED PVC FITTING & PIPE W/LATEX PAINT. HORIZTONAL SECTION OF CONDENSATE DRAIN DOES NOT HAVE ADEQUATE SLOPE. PROVIDE MIN 1/8" PER FT. ANCHOR PIPE TO WALL. 2.) PERMANETLY LABEL THE UNIT DATA PLATE W/PROPER HEAT KIT INSTALLED & SIZE CIRCUIT BREAKER ACCORDINGLY. 3.) UNIT F - REBUILD DRIAN TRAP ON AC UNIT. RECALL FOR INSPECTION. |