Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/20/2003 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000* | |
| 01/06/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*HARD WIRE SMOKE DETECTORS AT HALLWAY TOO AS WAS PREVIOUSLY WRITTEN UP LEAVE HALLWAY OPEN FOR INSP. | |
| 01/03/2003 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0999*ALL JUNCTION BOXES MUST BE READILY ACCESSIBLE WATER BONDS TO BE ACCESSIBLE PROVIDE A LETTER FROM THE ELECTRICAL CONTRACTOR DOING THIS WORK IT DOESN'T APPEAR WORK IS BEING DONE BY A LIC CONTRACTOR. IM SORRY IF I'M MISS READING THIS. HARD WIRE SMOKE DETECTORS AT ALL SLEEPING AREAS AND AT HALL. USE PROPER STRAP FOR SECURING FLEX CONDUIT. GROUND SCREWS MISSING AT RANGE RECEPT. EXIT ROOF W/E.M.T OR IMC RIGID NOT CARFLEX OR SEALTIGHT J-BOX TO FINISH WITHIN 1/4" OF FINISHED WALLS. |