Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/20/2003 | PLUMBING - FINAL | Approved | IVRS - Inspection 0000*PLUMBING FINAL COMPLETE AND OK. 2.) OK TO C OF O PENDING ANY OTHER INSPECTIONS. |
|
| 02/21/2003 | PLUMBING - FINAL | Not ready for Inspection | CODE VIOLATION ON RELIEFT LINE 1/2" LINE HAS BEEN INSTALLED PLEASE PROVIDE FULL SIZE RELIEF LINE 3/4 HAVE PLUMBER READ OVER 94UPC SEC 608.5. PLEASE NOT DRAIN SHALL NOT BE TRAPPED PROVIDE ACCESS TO ROOF AT TIME OF NEXT INSP. WE WILL CHECK VENT & VENT CAP HAVE PLUMBER CHECK COMBUSTION & RELIEF AIR SEE TABLE 5-1-94 UPC. |