Permit: T02CM04872

Parcel: 11102032B


Addresses:

3115 E PRINCE RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/12/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*OK FINAL SUBJECT TO OTHER INSPECTIONS.
01/08/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
1.) PLEASE CORRECTLY INSTALL GROUND BAR AS PER MANFACTURES INSTRUCTIONS.
2.) WE HAVE MUTLPOLE CONDUCTORS UNDER LUG TERMANATIONS AT BREAKERS
3.) PLEASE LABEL OUTSIDE COVER OF PANEL. LABEL TO E PERMANENT TO WITH SAND WETHER
4.) ENTRANCES ENTERING ABOVE CURRENT CARRING PARTS. TO HAVE A SEALING DEVICE.
5.) ALL METAL BOXES TO BE GROUNDED
6.) PLEASE VERIFY LICENSED CONTRACTOR PER NOTE ABOVE.