Inspection History Details
Permit: T02CM04810
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/13/2002 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000* | |
| 11/06/2002 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0245*NOTES 1.) MC CABLE MUST BE SUPPORTED WITHIN 12" EACH TERMINATION AND AT 6' INTERVALS 334-NEC. 2.) USE LISTED STRAPS FOR MC, 1/2 CONDUIT STRAPS NOT APPROVED. 110-3 NEC. 3.) USE LISTED AND APPROVED PLASTIC OR METAL BOXES FOR MC CABLE PLASTIC WAILON BOXES USED ARE FOR ROMEX. 4.) IF FLEXABLE CONDUIT IS USED WITH ROMEX RUN INSIDE, ROMEX MUST BE CLAMPED AT EACH END WITH APPROVED FITTINGS PER NEC. 5.) LEAVE NAME & PH OF L-11 LICENSED CONTR. DOING WORK. |